Brochures
The Fike NOVEC™ 1230 system is armed and ready to eliminate any fire hazard at a moment’s notice. Its 500 psi operating pressure provides ultimate design flexibility and ensures that the necessary amount of agent reaches every corner of the protected space in under ten seconds, extinguishing a fire in its very earliest stages.
The Fike extinguishing agent is ideal for protecting sensitive electronic equipment and irreplaceable items from fire and the damaging effects of fire sprinkler systems. It is electrically non-conductive, non-corrosive and leaves no residue behind after a system discharge.
3M™ Novec™ 1230 Fire Protection Fluid is a clear, colorless and low odor fluid. It is stored as a liquid and dispensed into the hazard as an electrically non‐conductive gaseous vapor that is clear and does not obscure vision.
The discharge nozzles are made of brass and are available in a 180° and 360° discharge patterns. The nozzles are designed to control the agent flow and to distribute the agent throughout the protected enclosure in a uniform, predetermined pattern and concentration.
Fike’s clean agent containers are painted steel containers available in various sizes and varying fill densities. Each container is fitted with an internal siphon tube, Fike Impulse Valve assembly, pressure gauge, container nameplate and applicable mounting hardware.
Check Valves are used to prevent agent loss from the open end of a manifold and/or piping system in the event that one or more containers are removed for servicing / maintenance.
After a system has been discharged, the container’s rupture disc valve must be rebuilt before the container can be recharged and placed back into service. The recharge kits contain all of the items required to rebuild the valve.
Mounting Straps / Brackets are used to secure containers to a wall or other suitable mounting surface.
The pressure gauge is mounted to each container to provide visual indication of the container pressure. The pressure gauge can be installed, removed or replaced on a charged container without removing the agent first.
The Liquid Level Indicator (LLi) provides a means of verifying the weight of agent in a container without having to remove the container and weigh it on a calibrated scale.
The low pressure switch (LPS) for systems using Novec 1230 fire protection fluid is an optional item that can be added to Impulse Valve containers for the purpose of continuously monitoring the container pressure for a low‐pressure condition.
Selector Valves allow a single agent supply to be utilized for protection of multiple hazards, reducing the total amount of agent required.
The Impulse Valve Pneumatic Operator (IVPO) provides the means to pneumatically activate the Fike Impulse Valve clean agent container by providing the force required to extend a piston that will open the rupture disc, allowing the agent to be released from the container
Discharge Pressure Switch (DPS) is used to provide a positive pneumatic confirmation to the control system that the Fike Fire Suppression system has been discharged.
The 1” and 3” Impulse Valves are a rupture disc (metal diaphragm), pressure operated device that allows the agent to be released from the container and into the protected enclosure via the associated piping network and discharge nozzle(s).
The Impulse Valve Operator Supervisor (IVOS) is used to monitor the presence of the Impulse Valve Operator (IVO).
3M™ Novec™ 1230 Fire Protection Fluid is a next-generation halon alternative offering outstanding performance, large margin of safety, and an excellent environmental profile.
To provide fire protection in the offices, equipment rooms and other confined spaces that form part of onshore and offshore oil and gas installations, halonbased extinguishing systems have, in the past, been a popular choice
Archives and museums are repositories for some of our most precious, delicate and usually irreplaceable documents and artifacts.
FM Approvals Class: 5612
Fire Protection Equipment.
Novec™ 1230 Clean Agent Fire Suppression Systems Pre-Engineered, Balanced and Engineered, Unbalanced 500psi (34.5 bar)
PRE-ENGINEERED UNITS 3M™ Novec™ 1230 Fire Protection Fluid (dodecafluoro-2-methylpentan-3-one) Extinguishing System Units, stored pressure type, having nominal charging capacities of 40, 76, 164, 322 and 601 lb (18.1, 34.5, 74.4, 146.1 and 272.6 kg) Novec™ 1230 Fluid, respectively. The units are super-pressurised to 25 bar (363 psig) with operating temperatures of 0 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
U.S. Department fo Homeland Security United States Coast Guard certificate of approval.
Nitrogen Safety Data Sheet
Novec 1230 Safety Data Sheet